ABC STORED PRESSURE TYPE FIRE EXTINGUISHERS
ISI mark ABC type fire extinguisher covers A, B, & C class of fires which includes paper, wood, cloth, rubber, plastic & inflammable liquids like oil, petrol, paints, petrochemical products, resins, gases in the compressed form like oxygen, acetylenes, LP & CNG, electrical & sophisticated electrical equipments.
TECHNICAL SPECIFICATION
| FIRE EXTINGUISHER CAPACITY |
1kg |
2kg |
4kg |
6kg |
9kg |
| MINIMUM PERIOD FOR WHICH |
IS-15683 |
IS-15683 |
IS-15683 |
IS-15683 |
IS-15683 |
| THROW OF JET MAINTAINED |
8 sec |
8 sec |
16 sec |
20 sec |
25 sec |
| MINIMUM PERIOD TO DISCHARGE |
- |
- |
- |
- |
- |
| AT LEAST 90% OF CONTESTS |
12 sec. |
16 sec. |
20 sec. |
25 sec. |
30 sec. |
| RANGE OF JET |
2 mtr. |
3 mtr. |
4 mtr. |
6 mtr. |
7 mtr. |
| EMPTY WT. (approx) |
1 kg |
2.3 kg |
2.75 kg |
3.3 kg |
5.35 kg |
| FULL WT. (approx) |
2 kg |
3.3 kg |
6.75 kg |
9.3 kg |
14.35 kg |
| FIRE RATING |
1 A, 8 B |
1 A, 8 B |
2 A, 21 B |
3 A, 34 B |
3 A, 34 B |
| WORKING PRESSURE |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
| HYDRO PRESSURE |
35 kgf/cm2 |
35 kgf/cm2 |
35 kgf/cm2 |
35 kgf/cm2 |
35 kgf/cm2 |
| BRUSTING PRESSURE |
55 kgf/cm2 |
55 kgf/cm2 |
55 kgf/cm2 |
55 kgf/cm2 |
55 kgf/cm2 |
WATER TYPE FIRE EXTINGUISHERS
ISI mark water type fire extinguishers provides safety against 'A' class of fire which involves materials like wood, paper, cloth, plastic, fibre & rubber, etc.,
TECHNICAL SPECIFICATION
| FIRE EXTINGUISHER CAPACITY |
6 litrestored pressure |
9 litrestored pressure |
9 litrecatridge type |
50 litre |
| MINIMUM PERIOD FOR WHICH |
IS-15683 |
IS-15683 |
IS-15683 |
IS-13385 |
| THROW OF JET MAINTAINED |
25 sec |
100 sec |
60 sec |
60 sec |
| MINIMUM PERIOD TO DISCHARGE |
- |
- |
- |
- |
| AT LEAST 90% OF CONTESTS |
60 sec. |
120 sec. |
180 sec. |
180 sec. |
| RANGE OF JET |
4 mtr. |
6 mtr. |
10 mtr. |
10 mtr. |
| EMPTY WT. (approx) |
03.20 kg |
05.35 kg |
35.00 kg |
35.00 kg |
| FULL WT. (approx) |
09.20 kg |
14.35 kg |
80.00 kg |
80.00 kg |
| FIRE RATING |
3 A |
3 A |
3 A |
NA |
| WORKING PRESSURE |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
| HYDRO PRESSURE |
35 kgf/cm2 |
35 kgf/cm2 |
30 kgf/cm2 |
30 kgf/cm2 |
| BRUSTING PRESSURE |
55 kgf/cm2 |
55 kgf/cm2 |
45 kgf/cm2 |
45 kgf/cm2 |
MECHANICAL FOAM TYPE FIRE EXTINGUISHERS
ISI mark foam type fire extinguisher is designed to extinguish 'A' & 'B' class of fire involving wood, paper, cloth, textile, stationery, flammable and volatile liquids like oil, petrol, kerosene, solvent, chemicals, wax, resins, etc.,
TECHNICAL SPECIFICATION
| FIRE EXTINGUISHER CAPACITY |
6 litrestored pressure |
9 litrestored pressure |
9 litrecatridge type |
50 litre |
| MINIMUM PERIOD FOR WHICH |
IS-15683 |
IS-15683 |
IS-15683 |
IS-13385 |
| THROW OF JET MAINTAINED |
35 sec |
35 sec |
35 sec |
40 sec |
| MINIMUM PERIOD TO DISCHARGE |
- |
- |
- |
- |
| AT LEAST 90% OF CONTESTS |
25 sec. |
60 sec. |
60 sec. |
180 sec. |
| RANGE OF JET |
6 mtr. |
3 mtr. |
6 mtr. |
10 mtr. |
| EMPTY WT. (approx) |
03.20 kg |
05.35 kg |
07.00 kg |
35.00 kg |
| FULL WT. (approx) |
09.20 kg |
14.35 kg |
16.00 kg |
80.00 kg |
| FIRE RATING |
2 A, 34 B |
3 A, 34 B |
4 A, 55 B |
NA |
| WORKING PRESSURE |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
| HYDRO PRESSURE |
35 kgf/cm2 |
35 kgf/cm2 |
35 kgf/cm2 |
30 kgf/cm2 |
| BRUSTING PRESSURE |
55 kgf/cm2 |
55 kgf/cm2 |
55 kgf/cm2 |
45 kgf/cm2 |
CARBON DIOXIDE TYPE FIRE EXTINGUISHERS
ISI mark carbon dioxide type fire extinguisher are suitable for 'B' & 'C' class fires involving all flammable liquids, gases, live & delicate, machinery fires, electrical & sophisticated electronic equipment fires, transformer & switch gear fire. This extinguisher is approved by explosive department, Govt. of India, Nagpur. The new CO2 squeeze grip type portable fire extinguisher from safety fire is also available.
TECHNICAL SPECIFICATION
| FIRE EXTINGUISHER CAPACITY |
2 kg |
3 kg |
4.5 kg |
6.5 kg |
9 kg |
22.5 kg |
| MINIMUM PERIOD FOR WHICH |
IS-15683 |
IS-15683 |
IS-15683 |
IS-2878 |
IS-2878 |
IS-2878 |
| THROW OF JET MAINTAINED |
8 sec |
8 sec |
8 sec |
10 sec |
15 sec |
20 sec |
| MINIMUM PERIOD TO DISCHARGE |
- |
- |
- |
- |
- |
- |
| AT LEAST 90% OF CONTESTS |
10 sec. |
16 sec. |
20 sec. |
20 sec. |
36 sec. |
60 sec. |
| RANGE OF JET |
2 mtr. |
3 mtr. |
3 mtr. |
4 mtr. |
4 mtr. |
4 mtr. |
| EMPTY WT. (approx) |
6.20 kg |
9.50 kg |
12.50 kg |
20.00 kg |
26.00 kg |
43.50 kg |
| FULL WT. (approx) |
8.20 kg |
12.50 kg |
17.00 kg |
26.50 kg |
35.00 kg |
66.00 kg |
| FIRE RATING |
13 B |
21 B |
21 B |
NA |
NA |
NA |
| WORKING PRESSURE |
60 kgf/cm2 |
60 kgf/cm2 |
60 kgf/cm2 |
60 kgf/cm2 |
60 kgf/cm2 |
60 kgf/cm2 |
| HYDRO PRESSURE |
250 kgf/cm2 |
250 kgf/cm2 |
250 kgf/cm2 |
250 kgf/cm2 |
250 kgf/cm2 |
250 kgf/cm2 |
| BRUSTING PRESSURE |
600 kgf/cm2 |
600 kgf/cm2 |
600 kgf/cm2 |
600 kgf/cm2 |
600 kgf/cm2 |
600 kgf/cm2 |
DRY CHEMICAL POWDER TYPE FIRE EXTINGUISHERS
ISI mark Dry Chemical Fire Extinguisher control 'A', 'B', & 'C' class of fire like wood, paper, cloth, oil, and petroleum product, solvents, paints, varnishes, chemical liquids. All flammable liquids & electrical fire & gas fire, etc.,
TECHNICAL SPECIFICATION
| FIRE EXTINGUISHER CAPACITY |
4 kg |
6 kg (ABC) |
9 kg (ABC) |
25 kg |
50 kg |
75 kg |
| MINIMUM PERIOD FOR WHICH |
IS-15683 |
IS-15683 |
IS-15683 |
IS-10658 |
IS-10658 |
IS-10658 |
| THROW OF JET MAINTAINED |
20 sec |
20 sec |
25 sec |
25 sec |
40 sec |
50 sec |
| MINIMUM PERIOD TO DISCHARGE |
- |
- |
- |
- |
- |
- |
| AT LEAST 90% OF CONTESTS |
25 sec. |
25 sec. |
30 sec. |
30 sec. |
50 sec. |
60 sec. |
| RANGE OF JET |
4 mtr. |
4 mtr. |
6 mtr. |
6 mtr. |
8 mtr. |
10 mtr. |
| EMPTY WT. (approx) |
4.20 kg |
5.20 kg |
7.05 kg |
30 kg |
60 kg |
75 kg |
| FULL WT. (approx) |
8.20 kg |
11.20 kg |
16.05 kg |
55.00 kg |
110.00 kg |
150.00 kg |
| FIRE RATING |
2 A, 21 B |
3 A, 34 B |
4 A, 34 B |
NA |
NA |
NA |
| WORKING PRESSURE |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
| HYDRO PRESSURE |
35 kgf/cm2 |
35 kgf/cm2 |
35 kgf/cm2 |
30 kgf/cm2 |
30 kgf/cm2 |
30 kgf/cm2 |
| BRUSTING PRESSURE |
55 kgf/cm2 |
55 kgf/cm2 |
55 kgf/cm2 |
45 kgf/cm2 |
45 kgf/cm2 |
45 kgf/cm2 |
CLEAN AGENT TYPE FIRE EXTINGUISHERS
Suitable for 'A', 'B', & 'C' class fire. Can be used in computer room, telecommunications facilities, laboratories, hospital, offices, server rooms, call centers, banks, ships, etc.,
TECHNICAL SPECIFICATION
| FIRE EXTINGUISHER CAPACITY |
1 kg |
2 kg |
4 kg |
6 kg |
| MINIMUM PERIOD FOR WHICH |
- |
IS-15683 |
IS-15683 |
IS-15683 |
| THROW OF JET MAINTAINED |
8 sec |
8 sec |
16 sec |
20 sec |
| MINIMUM PERIOD TO DISCHARGE |
- |
- |
- |
- |
| AT LEAST 90% OF CONTESTS |
10 sec. |
16 sec. |
20 sec. |
25 sec. |
| RANGE OF JET |
- |
1 mtr. |
1 mtr. |
2 mtr. |
| EMPTY WT. (approx) |
1.20 kg |
2.30 kg |
2.75 kg |
3.30 kg |
| FULL WT. (approx) |
2.20 kg |
4.30 kg |
6.75 kg |
9.30 kg |
| FIRE RATING |
8 B |
13 B |
1 A, 21 B |
1 A, 34 B |
| WORKING PRESSURE |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
15 kgf/cm2 |
| HYDRO PRESSURE |
35 kgf/cm2 |
35 kgf/cm2 |
35 kgf/cm2 |
35 kgf/cm2 |
| BRUSTING PRESSURE |
55 kgf/cm2 |
55 kgf/cm2 |
55 kgf/cm2 |
55 kgf/cm2 |